Modeling CRACs in Service Galleries

intermediate
Two ways to model computer room air conditioner units in a service gallery: block the gallery out, or mesh it and duct the supply under the floor.

This video shows two ways to model computer room air conditioner (CRAC) units that sit in a service gallery outside the white space. The demo uses a raised floor room with a ceiling return plenum.

What the video shows

  1. Enlarge the default room to leave space for the gallery, drag larger CRAC units in from the library, and copy and paste them into position.
  2. Method one: block out the gallery. Add a column block (slab to slab) behind each unit so the gallery volume is not meshed. The cooling units then act like supply ducts feeding the room.
  3. Match the block and unit dimensions by keeping two editors open and comparing start positions and lengths. Blocks must sit tight against the units and walls.
  4. Method two: mesh the gallery. Add a baffle (a zero-thickness object, so it uses few mesh cells) to form the wall, and set a small leakage so the sealed volume is not a dead zone.
  5. Add blocks in the plenum around each unit to create a supply duct under the floor, and turn on the plenum extension switch so each unit connects to the ceiling.
  6. Lay out racks, ceiling grills and loads, then run the model and review the HTML report.

Tips

  • Gaps between blocks, units and walls make the mesher create many small cells and raise the cell count.
  • Dragging an object slightly out of the room lets the auto repair snap it back tight against the wall.
  • The presenter prefers the block-out method because it needs fewer mesh cells, though either works.
  • Align racks as closely as possible: a cleaner layout gives a smaller mesh, a faster run and better results.