All training

Pedestal CRAC Unit Demonstration

intermediate
How to model downflow CRAC units on pedestals in a non-raised floor room, run the job, and review the emailed summary and the results.

This video builds a small non-raised floor data hall with downflow computer room air conditioner (CRAC) units standing on pedestals, then runs the model and reviews the results.

What the video shows

  1. Change the room type to non-raised floor with a ceiling plenum supply.
  2. Drag in a CRAC unit, change it from the default in-row type to a downflow unit, and lift it off the floor so its outlet is not blocked. The demo sets it about 3 feet up, with a 70 degree Fahrenheit supply temperature. No pedestal object is needed.
  3. Drag the unit out of the room and let it snap back so it sits against the wall. Copy and paste a second unit.
  4. Add a row of racks at 4 kilowatts each and a ceiling grill sized to match the row.
  5. Save and run the job. The job is sent to the remote simulation facility, and the user receives emails when it starts and finishes, including the cooling audit summary report.
  6. Download the results into the output tab. The input model and output model stay in separate tabs so the two always match.
  7. Review the ASHRAE recommended range display, path lines from the units and racks, cut planes and animations, and export the report.